Journal of Shandong University(Engineering Science) ›› 2020, Vol. 50 ›› Issue (3): 98-103.doi: 10.6040/j.issn.1672-3961.0.2019.575

• Electrical Engineering • Previous Articles     Next Articles

Multi-infeed HVDC simultaneous commutation failure risk evaluation method considering synchronous condenser reactive power

Changhui MA1(),Liang WANG2,Shaoqing TAN3,Yi LU3,*(),Huan MA1,Kang ZHAO1   

  1. 1. State Grid Shandong Electric Power Research Institute, Jinan 250002, Shandong, China
    2. State Grid Shandong Electric Power Company, Jinan 250001, Shandong, China
    3. Key Laboratory of Power System Intelligent Dispatch and Control of Ministry of Education (Shandong University), Jinan 250061, Shandong, China
  • Received:2019-10-08 Online:2020-06-20 Published:2020-06-16
  • Contact: Yi LU E-mail:machanghui@163.com;luyi_ee@mail.sdu.edu.cn
  • Supported by:
    国网山东省电力公司科技资助项目

Abstract:

In order to improve the "Strong alternating current and weak direct current" characteristics of multi-infeed high voltage direct current systems, the synchronous condenser gradually gained attention.For the problem of multi-infeed high voltage direct current with synchronous condenser simultaneous commutation failure, a risk evaluation method considering the synchronous condenser reactive voltage characteristics was proposed. Firstly, the reactive voltage characteristics of the synchronous condenser were analyzed, and the multi-infeed interaction factor was calculated by reactive voltage sensitivity of the synchronous condenser, high voltage direct current system and static reactive power compensation device. Then, based on the nature of the commutation failure, the commutation failure evaluation factor was defined, and the simultaneous commutation failure risk of the multi-infeed high voltage direct current system with synchronous condenser was evaluated. Finally, the Shandong power grid was taken as an example to verify the results that the proposed method could effectively evaluate the multi-infeed high voltage direct current simultaneous commutation failure, and it was important in the early planning of the high voltage direct current transmission system and ensuring the stability and security of the power system.

Key words: multi-infeed HVDC, simultaneous multi-HVDC commutation failures, synchronous condenser, multi-infeed interaction factor, commutation failure estimate factor

CLC Number: 

  • TM721.1

Fig.1

Diagram of Shandong power grid under AC/DC access"

Table 1

The CFEF of Shangdong HVDC system"

直流名称昭沂低端昭沂高端鲁固低端鲁固高端银东直流
CFEF0.103 10.104 50.165 60.164 20.145 7

Table 2

MIIF of Shangdong HVDC system without synchronous condenser"

待评估直流故障直流
沂南智圣鸢都青州胶东
临特0.355 670.264 280.571 400.433 38
智圣0.295 720.304 440.534 860.349 55
鸢都0.211 110.292 540.442 330.352 02
青州0.243 340.273 640.235 730.262 29
胶东0.215 510.208 940.219 100.306 58

Table 3

MIIF of Shangdong HVDC system with synchronous condenser"

待评估直流故障直流
沂南智圣鸢都青州胶东
临特0.355 190.263 320.570 020.432 20
智圣0.293 600.302 190.531 140.346 85
鸢都0.210 440.292 210.441 260.351 11
青州0.242 830.273 430.235 140.261 52
胶东0.215 110.208 730.218 640.305 85

Fig.2

DC operation of Shandong grid after Zhisheng short-circuit"

Table 4

Simulation results of Shangdong DC system"

待评估直流故障直流
沂南智圣昌乐青州胶东
昭沂换相失败换相失败换相失败
鲁固换相失败换相失败换相失败
银东换相失败换相失败换相失败换相失败
1 郭春义, 赵剑, 刘炜, 等. 抑制高压直流输电系统换相失败方法综述[J]. 中国电机工程学报, 2018, 38 (增刊1): 1- 10.
GUO Chunyi , ZHAO Jian , LIU Wei , et al. A review of methods to mitigate the commutation failure for LCC-HVDC[J]. Proceedings of the CSEE, 2018, 38 (Suppl.1): 1- 10.
2 田世明, 栾文鹏, 张东霞, 等. 能源互联网技术形态与关键技术[J]. 中国电机工程学报, 2015, 35 (14): 3482- 3494.
TIAN Shiming , LUAN Wenpeng , ZHANG Dongxia , et al. Technical formsand key technologies on energy internet[J]. Proceedings of the CSEE, 2015, 35 (14): 3482- 3494.
3 CAO Yongji , ZHANG Yi , ZHANG Hengxu , et al. Probabilistic optimal PV capacity planning for wind farm expansion based on NASA data[J]. IEEE Transactions on Sustainable Energy, 2017, 8 (3): 1291- 1300.
doi: 10.1109/TSTE.2017.2677466
4 李志强, 蒋维勇, 王彦滨, 等. 大容量新型调相机关键技术参数及其优化设计[J]. 大电机技术, 2017, (4): 15- 22.
doi: 10.3969/j.issn.1000-3983.2017.04.004
LI Zhiqiang , JIANG Weiyong , WANG Yanbin , et al. Key technical parameters and optimal design of new types of large capacity synchronous condenser[J]. Large Electric Machine and Hydraulic Turbine, 2017, (4): 15- 22.
doi: 10.3969/j.issn.1000-3983.2017.04.004
5 王增平, 刘席洋, 李林泽, 等. 多馈入直流输电系统换相失败边界条件[J]. 电工技术学报, 2017, 32 (10): 12- 19.
WANG Zengping , LIU Xiyang , LI Linze , et al. Boundary conditions of commutation failure in multi-infeed HVDC systems[J]. Transactions of China Electro Technical Society, 2017, 32 (10): 12- 19.
6 邵瑶, 汤涌. 一种快速评估多馈入直流系统换相失败风险的方法[J]. 中国电机工程学报, 2017, 37 (12): 3429- 3436.
SHAO Yao , TANG Yong . A fast assessment method for evaluating commutation failure risk of multi-infeed HVDC system[J]. Proceedings of the CSEE, 2017, 37 (12): 3429- 3436.
7 肖浩, 李银红, 于芮技, 等. 影响多馈入直流系统换相失败的电网薄弱区域快速识别方法[J]. 中国电机工程学报, 2016, 36 (7): 1781- 1789.
XIAO Hao , LI Yinhong , YU Ruizhi , et al. A rapid identification method of weak areas in power grid based on commutation failure analysis in multi-infeed HVDC systems[J]. Proceedings of the CSEE, 2016, 36 (7): 1781- 1789.
8 金一丁, 于钊, 李明节, 等. 新一代调相机与电力电子无功补偿装置在特高压交直流电网中应用的比较[J]. 电网技术, 2018, 42 (7): 2095- 2102.
JIN Yiding , YU Zhao , LI Mingjie , et al. Comparison of new generation synchronous condenser and power electronicreactive-power compensation devices in application in UHV DC/AC grid[J]. Power System Technology, 2018, 42 (7): 2095- 2102.
9 蒋维勇,戚庆茹.在"强直弱交"混联电网为什么要安装调相机?[N].国家电网报, 2016-8-6(6).
10 CIGRE Working Group B4.41.Systems with multiple DC infeed[R]. Paris, France: CIGRE, 2008.
11 XU Xin , CAO Yongji , ZHANG Hengxu , et al. A multi-objective optimization approach for corrective switching of transmission systems in emergency scenarios[J]. Energies, 2017, 10 (8): 1204.
doi: 10.3390/en10081204
12 王徭. 特高压直流输电控制与保护技术的研究[J]. 电力系统保护与控制, 2009, 37 (15): 53- 58.
WANG Yao . Study on the control and protection system of ultra highvoltage direct current transmission[J]. Power System Protection and Control, 2009, (15): 53- 58.
13 THIO C V , DAVIES J B , KENT K L . Commutation failuresin HVDC transmission systems[J]. IEEE Transactions on Power Delivery, 1996, 32 (11): 946- 957.
14 HANSEN A , HAVEMANN H . Decreasing the commutationfailure frequency in HVDC transmission systems[J]. IEEE Transactions on Power Delivery, 2000, 15 (10): 1022- 1026.
15 RAHIMI E , GOLE A M , DAVIES J B . Commutation failure analysis in multi-infeed HVDC systems[J]. IEEE Transactions on Power Delivery, 2011, 23 (11): 378- 384.
16 ZHANG Hengxu , CAO Yongji , ZHANG Yi . Quantitative synergy assessment of regional wind-solar energy resources based on MERRA reanalysis data[J]. Applied Energy, 2018, 216, 172- 182.
doi: 10.1016/j.apenergy.2018.02.094
17 邵瑶, 汤涌. 多馈入直流系统交互作用因子的影响因素分析[J]. 电网技术, 2013, 37 (3): 794- 799.
SHAO Yao , TANG Yong . Analysis of influencing factors of multi-infeed HVDC system interaction factor[J]. Power System Technology, 2013, 37 (3): 794- 799.
18 林伟芳, 汤涌, 郭小江. 多馈入交直流系统短路比影响因素分析[J]. 电网技术, 2011, 35 (8): 64- 68.
LIN Weifang , TANG Yong , GUO Xiaojiang . Analysis of influencing factors of short circuit ratio of multi-infeed AC/DC power system[J]. Power System Technology, 2011, 35 (8): 64- 68.
No related articles found!
Viewed
Full text


Abstract

Cited

  Shared   
  Discussed   
[1] ZHANG Yong-hua,WANG An-ling,LIU Fu-ping . The reflected phase angle of low frequent inhomogeneous[J]. JOURNAL OF SHANDONG UNIVERSITY (ENGINEERING SCIENCE), 2006, 36(2): 22 -25 .
[2] KONG Xiang-zhen,LIU Yan-jun,WANG Yong,ZHAO Xiu-hua . Compensation and simulation for the deadband of the pneumatic proportional valve[J]. JOURNAL OF SHANDONG UNIVERSITY (ENGINEERING SCIENCE), 2006, 36(1): 99 -102 .
[3] CHEN Rui, LI Hongwei, TIAN Jing. The relationship between the number of magnetic poles and the bearing capacity of radial magnetic bearing[J]. JOURNAL OF SHANDONG UNIVERSITY (ENGINEERING SCIENCE), 2018, 48(2): 81 -85 .
[4] WANG Bo,WANG Ning-sheng . Automatic generation and combinatory optimization of disassembly sequence for mechanical-electric assembly[J]. JOURNAL OF SHANDONG UNIVERSITY (ENGINEERING SCIENCE), 2006, 36(2): 52 -57 .
[5] LI Ke,LIU Chang-chun,LI Tong-lei . Medical registration approach using improved maximization of mutual information[J]. JOURNAL OF SHANDONG UNIVERSITY (ENGINEERING SCIENCE), 2006, 36(2): 107 -110 .
[6] QIN Tong, SUN Fengrong*, WANG Limei, WANG Qinghao, LI Xincai. 3D surface reconstruction using the shape based interpolation guided by maximal discs[J]. JOURNAL OF SHANDONG UNIVERSITY (ENGINEERING SCIENCE), 2010, 40(3): 1 -5 .
[7] LIU Wen-liang, ZHU Wei-hong, CHEN Di, ZHANG Hong-quan. Detection and tracking of moving targets using the morphology match in radar images[J]. JOURNAL OF SHANDONG UNIVERSITY (ENGINEERING SCIENCE), 2010, 40(3): 31 -36 .
[8] ZHANG Ying,LANG Yongmei,ZHAO Yuxiao,ZHANG Jianda,QIAO Peng,LI Shanping . Research on technique of aerobic granular sludge cultivationby seeding EGSB anaerobic granular sludge[J]. JOURNAL OF SHANDONG UNIVERSITY (ENGINEERING SCIENCE), 2006, 36(4): 56 -59 .
[9] SUN Dianzhu, ZHU Changzhi, LI Yanrui. [J]. JOURNAL OF SHANDONG UNIVERSITY (ENGINEERING SCIENCE), 2009, 39(1): 84 -86 .
[10] YUE Yuan-Zheng. Relaxation in glasses far from equilibrium[J]. JOURNAL OF SHANDONG UNIVERSITY (ENGINEERING SCIENCE), 2009, 39(5): 1 -20 .